5.3 Alarm Detection

Note:

Digital operator display text is represented in the tables below using standard font for both LCD displays and LED displays. When using

the standard LED operator, however, display text will appear in 7-segment LED (ex: “

”). When the LED fault display differs from the

LCD display, the LED display text will be shown in parentheses under the LCD display text.

u

Alarm Codes, Causes, and Possible Solutions

Alarms are drive protection functions that do not necessarily cause the drive to stop. After removing the cause of an alarm,

the drive will return to its previous status before the alarm occurred.
When an alarm has been triggered, the ALM light on the digital operator display blinks and the alarm code display flashes. If

a multi-function output is set for an alarm (H2-oo = 10), that output terminal will be triggered.

Note:

If a multi-function output is set to close when an alarm occurs (H2-oo = 10), it will also close when maintenance periods are reached,

triggering alarms LT-1 through LT-4 (triggered only if H2-oo = 2F).

Table 5.3 Alarm Codes, Causes, and Possible Solutions

Digital Operator Display

Minor Fault Name

AEr

Station Address Setting Error (CC-Link, CANopen, MECHATROLINK)
Option card node address is outside the acceptable setting range.

Cause

Possible Solution

Station number is set outside the possible

setting range.

• Set parameter F6-10 to the proper value if a CC-Link option card is used
• Set parameter F6-20 to the proper value if a MECHATROLINK option card is used.
• Set parameter F6-35 to the proper value if a CANopen option card is used.

Digital Operator Display

Minor Fault Name

AnalogFB Lost

Switched to Net

(AFBL)

Analog Feedback Lost

Analog feedback has not been detected and the network PID feedback signal is now used.

Cause

Possible Solution

Defective or broken analog input source.

Confirm that the PID feedback source is installed and working properly. If there is no feedback source, set

P9-02 to 3 so the drive will read the network PID feedback from another drive.

H3-0o is not set to B (PID Feedback)

Set H3-0o to B if the analog input source is to be used for PID feedback.

Set P9-02 to 3 if the drive does not have an analog PID feedback source.

Digital Operator Display

Minor Fault Name

Anti-Jam Active

(AJA)

Anti-Jam Alarm

Cause

Possible Solution

The drive is attempting to clear debris from

the impeller. This is only effective when

P7-01, Anti-jam Operation is set to 1

(enabled).

• Alarm will clear when function is complete.
• Drive response to this condition is controlled by P7-01, Anti-jam Operation Selection.

Digital Operator Display

Minor Fault Name

bAT

Digital Operator Battery Voltage Low

Cause

Possible Solution

The digital operator battery is low

Replace the digital operator battery.

Digital Operator Display

Minor Fault Name

bb

Baseblock
Drive output interrupted as indicated by an external baseblock signal.

Cause

Possible Solution

External baseblock signal was entered via

one of the multi-function input terminals

(S1 to S7).

Check external sequence and baseblock signal input timing.

Digital Operator Display

Minor Fault Name

bUS

Option Communication Error
• The connection was lost after initial communication was established.
• Assign a Run command frequency reference to the option.

5.3 Alarm Detection

180

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual