Yaskawa iQpump Micro User Manual

Page 232

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-09

(01AD)

PID Output Level

Selection

Output Level Sel

0: Direct Acting

1: Inverse Acting

0: Direct acting

1: Inverse acting

Default: 0

Range: 0, 1

128

b5-10

(01AE) PID Output Gain Setting Output Gain

Sets the gain applied to the PID output.

Default: 1.00

Min.: 0.00

Max.: 25.00

b5-11

(01AF)

PID Output Reverse

Selection

Output Rev Sel

0: 0 limit

1: Reverse

0: Negative PID output triggers zero limit.

1: Rotation direction reverses with negative PID output.

Note:

When using setting 1, make sure reverse

operation is permitted by b1-04.

Default: 0

Range: 0, 1

b5-12

(01B0)

Feedback Loss 4 to 20

mA Detection Selection

Fdbk 4-20mA Det

0: Disabled

1: Alarm only

2: Fault

3: Run At b5-13

Performs a 4 to 20 mA wire break detection on the analog input

that is programmed for PID feedback.

0: Disabled

1: Alarm only

2: Fault

3: Run at b5-13

Default: 2

Range: 0 to 3

b5-13

(01B1)

Feedback Loss Goto

Frequency

FdbkLossGotoFreq

Sets the speed at which the drive will run if a 4 to 20 mA wire

break is detected on the PID Feedback and when b5-12 is set to

3 (Run at b5-13).

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

b5-14

(01B2) Feedback Loss of Prime

Level

FdbkLoss LOP Lvl

Detects loss of prime in the pump when a wire break condition

has occurred.

When the measured quantity determined by P1-18 (output

current, kilowatts, or power) drops below this level for the time

set in P1-20 and the output frequency is at the level set in b5-13,

a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<1>

Min.: 0.0

Max.: 1000.0

b5-15

(01B3) Feedback Loss Go To

Frequency Time Out

FdbkLossGotoTimO

When b5-12 = 3 and the Feedback signal is lost, the drive will

run at the b5-13 speed for the b5-15 time, after which the drive

will fault on Feedback Loss (FDBKL).

Timeout is disabled when set to 0sec and the drive will run

indefinitely at b5-13.

Default: 0 s

Min.: 0

Max.: 6000

b5-16

(01B4) Feedback Loss Start

Delay

FdbkLossStartDly

When an AUTO Run command is initiated, the drive will not

fault on Feedback Loss (FDBKL) or use the Feedback Loss

GoTo Frequency (b5-13) until the b5-16 time has expired.

Default: 0.0 s

Min.: 0.0

Max.: 120.0

b5-17

(01B5) PID Accel/Decel Time PID Acc/Dec Time

Sets the acceleration and deceleration time to PID setpoint.

Default: 0 s

Min.: 0

Max.: 255

b5-32

(01EE) Integrator Ramp Limit IntegratrRampLim

When set to a value greater than zero, the PID Integrator is

forced to be within +/- this amount of the soft starter output.

Default: 0.0 Hz

Min.: 0.0

Max.: 10.0

b5-34

(019F) PID Output Lower Limit PID Out Low Lim

Sets the minimum output possible from the PID controller as a

percentage of the maximum output frequency.

Default: 0.00%

Min.: -100.00

Max.: 100.00

b5-35

(01A0) PID Input Limit

PID Input Limit

Limits the PID control input (deviation signal) as a percentage

of the maximum output frequency. Acts as a bipolar limit.

Default:

1000.0%

Min.: 0.0

Max.: 1000.0

b5-39

(01FF)

PID System Units

Display Digits

PID UsrDspDigits

0: No Dec (XXXXX)

1: 1 Dec (XXX.X)

2: 2 Dec (XX.XX)

3: 3 Dec (XX.XXX)

Determines the number of digits in the user-defined display for

the PID parameters and monitors (Q1-oo, U5-99, etc).

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

Default: 1

Range: 0 to 3

128

b5-40

(017F)

Frequency Reference

Monitor Content during

PID

Fref Mon Sel@PID

0: Fref Mon w PID

1: Fref Mon w/o PID

0: Display the frequency reference (U1-01) after PID

compensation has been added.

1: Display the frequency reference (U1-01) before PID

compensation has been added.

Default: 0

Range: 0, 1

b5-47

(017D)

Reverse Operation

Selection 2 by PID

Output

Output Rev Sel2

0: 0 Limit

1: Reverse

0: Zero limit when PID output is a negative value.

1: Reverse operation when PID output is a negative value

(Zero limit if the reverse operation is prohibited by b1-04).

Default: 1

Range: 0, 1

<1> Unit text is set by P1-18, Prime Loss Detection Method.

B.2 b: Application

232

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual