Drive replacement, Serviceable parts, Terminal board overview – Yaskawa iQpump Micro User Manual

Page 211: Dismantling the removable terminal block, 4 drive replacement

Advertising
background image

6.4 Drive Replacement

u

Serviceable Parts

The drive contains few serviceable parts. The following parts are considered replacement parts on the drive:
• Main control board and I/O Terminal board I/O PCBs.
• Cooling fan(s)
• Front cover
Replace the drive if the main power circuitry is damaged. Contact your local Yaskawa representative before replacing parts

if the drive is still under warranty. Yaskawa reserves the right to replace or repair the drive according to Yaskawa warranty

policy.
On IP66/NEMA Type 4X enclosure drives, replace the entire unit (drive, enclosure, and heatsink) in the event that any single

part becomes damaged. The drive, waterproof/dustproof enclosure, and heatsink are constructed as a single piece, and it is not

possible to replace the drive separately from the protective enclosure.

WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious

personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the

power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock,

wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

u

Terminal Board Overview

The drive has a modular I/O terminal block that facilitates quick drive replacement. The terminal board contains on-board

memory that stores all drive parameter settings and allows the parameters to be saved and transferred to the replacement drive

by disconnecting the terminal board from the damaged drive then reconnecting the terminal board to the replacement drive.

There is no need to manually reprogram the replacement drive.

Note:

When transferring the removable terminal block with backup memory to a drive with a different voltage class or different output capacity,

set A1-03 to 2220 to initialize the drive after installing the terminal block.

A

B

C

A – Charge LED
B – Terminal Board Locking Pin

C – Removable Terminal Board

Figure 6.13 Terminal Board

u

Dismantling the Removable Terminal Block

WARNING! Electrical Shock Hazard. Never connect or disconnect wiring, remove connectors or option cards, or replace the cooling fan

while the power is on. Failure to comply may result in serious injury. Before servicing, disconnect all power to the equipment. The internal

capacitor remains charged even after the power supply is turned off.

WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in

serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation,

adjustment and maintenance of AC drives.

NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.

Failure to comply may result in ESD damage to the drive circuitry.

1.

Loosen the screw on the front of the drive and remove the front cover.

6.4 Drive Replacement

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

211

6

Periodic Inspection & Maintenance