L4: speed detection, L5: fault restart – Yaskawa iQpump Micro User Manual

Page 257

Advertising
background image

u

L4: Speed Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L4-01

(0499)

Speed Agreement

Detection Level

Spd Agree Level

L4-01 sets the frequency detection level for digital output

functions H2-oo = 2, 3, 4, 5.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

L4-02

(049A)

Speed Agreement

Detection Width

Spd Agree Width

L4-02 sets the hysteresis or allowable margin for speed

detection.

Default: 2.0

Min.: 0.0

Max.: 20.0

L4-03

(049B)

Speed Agreement

Detection Level (+/-)

Spd Agree Lvl+-

L4-03 sets the frequency detection level for digital output

functions H2-oo = 13, 14, 15, 16.

Default: 0.0 Hz

Min.: -400.0

Max.: 400.0

L4-04

(049C)

Speed Agreement

Detection Width (+/-)

Spd Agree Wdth+-

L4-04 sets the hysteresis or allowable margin for speed

detection.

Default: 2.0

Min.: 0.0

Max.: 20.0

L4-05

(049D)

Frequency Reference

Loss Detection

Selection

Ref Loss Sel

0: Stop

1:

Run@L4-06PrevRef

0: Stop. Drive stops when the frequency reference is lost.

1: Run. Drive runs at a reduced speed when the frequency

reference is lost.

Default: 0

Range: 0, 1

L4-06

(04C2)

Frequency Reference at

Reference Loss

Fref at Floss

Sets the percentage of the frequency reference that the drive

should run with when the frequency reference is lost.

Default: 80.0%

Min.: 0.0

Max.: 100.0

L4-07

(0470)

Speed Agreement

Detection Selection

Freq Detect Sel

0: No Detection @BB

1: Always Detected

0: No detection during baseblock.

1: Detection always enabled.

Default: 0

Range: 0, 1

u

L5: Fault Restart

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L5-01

(049E)

Number of Auto Restart

Attempts

Num of Restarts

Sets the number of times the drive may attempt to restart after

the following faults occur: GF, LF, oC, oH1, ov, PF, rH, rr, oL1,

oL2, oL3, oL4, STo, Uv1.

Default: 5

Min.: 0

Max.: 10

151

L5-02

(049F)

Auto Restart Fault

Output Operation

Selection

Restart Sel

0: Flt Outp Disabld

1: Flt Outp Enabled

0: Fault output not active.

1: Fault output active during restart attempt.

Default: 0

Range: 0, 1

L5-04

(046C)

Fault Reset Interval

Time

Flt Reset Wait T

Sets the amount of time to wait between performing fault

restarts.

Default: 20.0 s

Min.: 10.0

Max.: 3600.0

152

L5-40

(0670)

Low Feedback Fault

Retry Selection

Low Feedback

0: No retry

1: Retry

Determines whether the LFB-Low Feedback fault can be auto-

restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-41

(0671)

High Feedback Fault

Retry Selection

High Feedback

0: No retry

1: Retry

Determines whether the HFB-High Feedback fault can be auto-

restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-42

(0672)

Feedback Loss Fault

Retry Selection

Feedback Loss

0: No retry

1: Retry

Determines whether the FBL-Feedback Loss fault can be auto-

restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-50

(067A)

Setpoint Not Met Retry

Selection

SetPoint Not Met

0: No retry

1: Retry

Determines whether the NMS-Setpoint not Met fault can be

auto-restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-51

(067B)

Loss of Prime Fault

Retry Selection

High Feedback

0: No retry

1: Retry

Determines whether the LOP-Loss of Prime fault can be auto-

restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

B.8 L: Protection Function

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

257

B

Parameter List

Advertising
This manual is related to the following products: