Figure 3.1, Iqpumpmicro, 1 standard connection diagram – Yaskawa iQpump Micro User Manual

Page 61

Advertising
background image

+

-

1 MCCB

MC

2 MCCB

r1

s1

t1

<3>

R/L1

S/L2

T/L3

For single-phase

200 V power supply

use R/L1 and S/L2.

Three phase

power supply

for 200 V / 400 V

Terminals +1, +2, − , B1, and B2
are for connecting options.
Never connect power supply
lines to these terminals.

Digital inputs
(default setting)

Forward run/stop

Not Used

External
pump fault

Fault reset

HAND Mode

S1

S2

S3

S4

S5

S6

S7

Multi-
setpoint 1

<4>

DC link choke
(option)

iQpumpMicro

Thermal relay

(option)

Main circuit

Control circuit

R/L1

S/L2

T/L3

<1>

<2>

-

B1

+1

+2

B2

Jumper

Motor

Cooling fan

Braking resistor

(option)

U/T1

V/T2

W/T3

M

M

r1

s1

t1

FU

FV
FW

U

V

W

Ground
10 or less (400 V class)
100 or less (200 V class)

Digital output
250 Vac, 10 mA to 1 A
30 Vdc, 10 mA to 1 A
(default setting)

Option card

connector

Fault

MA

P1

MB

MC

P2

MP

PC

During Run
(photocoupler 1)

Fault
(photocoupler 2)

Photocoupler
output common

Digital output

5 to 48 Vdc
2 to 50 mA

(default setting)

Pulse train output

0 to +10 Vdc
(2 mA)

Comm.
connector

AM

AC

AM

0 to 32 kHz

Analog monitor
output

Termination
resistor

Monitor
output

<6>

IG

R+

R-

S+

S-

MEMOBUS/
Modbus comm.
RS-485/422

120 , 1/2 W

Cable shield ground

DIP
switch
S2

main circuit terminal

shielded line

twisted-pair shielded line

control terminal

Safe Disable
Input

Safety switch

HC

H1

Jumper

<7>

System feedback,

HAND speed,

Main speed reference

Multi-function

programmable

RP

+V

A1

A2

AC

2 k

Pulse train input
(max. 32 kHz)

0 to +10 V (20 k )

Setting power supply
+10.5 max. 20 mA

0 to +10 V (20 k )

(0)4 to 20 mA (250 )

DIP
switch S3

Shield ground

terminal

0 V

SC

Sink

Source

<5>

24 V

+24 V 8 mA

Wiring sequence should shut off

power to the drive when a fault

<8>

output is triggered.

TRX

ON

OFF

THRX

SA

1

2

TRX

MC

MC

MB

TRX

Fault relay contact

Braking resistor unit

Thermal relay trip contact

MC

SA

SA

THRX

V

I

DIP switch S1

HAND Mode 2

Refer to “Transducer 2-Wire Connection Diagram”
and “Transducer 3-Wire Connection Diagram” figures
on the following pages for details on 24 V Power Supply
connections.

Figure 3.1 Drive Standard Connection Diagram

3.1 Standard Connection Diagram

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

61

3

Electrical Installation