H2: multi-function digital outputs – Yaskawa iQpump Micro User Manual

Page 248

Advertising
background image

H1-oo

Setting

Function

LCD Display

Description

Page

90

High Water Level

High Water

Function active when the drive is running. Function logic depends on P1-31, High

Water Digital Input Configuration.

P1-31 = 0 (Normally open)

Closed: High water level fault

Open: Reservoir/Tank is filled to normal level

P1-31 = 1 (Normally closed)

Closed: Reservoir/Tank is filled to normal level

Open: High water level fault

95

Remove Drive Disable Remote Drv Disbl

Closed: Prevents the drive from running when active for the time set in P4-26.

Must be inactive for the time set in P4-27 to allow the drive to run again.

Note:

1. Parameter P4-25 determines if this input is normally open or

normally closed.

2. When P1-01 = 3, an alarm condition will cause this drive to be

unavailable to the network.

AF

Emergency Override

Forward Run

EmergOverrideFWD Closed: Run the drive forward using the speed set in S6-02.

B0

Emergency Override

Reverse Run

EmergOverrideREV

Closed: Run the drive in reverse using the speed set in S6-02.

u

H2: Multi-Function Digital Outputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H2-01

(040B)

Terminal MA, MB, and

MC function selection

(relay)

MA/MB/MC FuncSel

Refer to H2 Multi-Function Digital Output Settings on pages

248

to

250

for descriptions of setting values.

Default: E

Range: 0 to 1AA

140

H2-02

(040C)

Terminal P1 function

selection (open-

collector)

P1/PC Func Sel

Default: 37

Range: 0 to 1AA

140

H2-03

(040D)

Terminal P2 function

selection (open-

collector)

P2/PC Func Sel

Default: E

Range: 0 to 1AA

140

H2-06

(0437)

Watt Hour Output Unit

Selection

Pwr Mon Unit Sel

Outputs a 200 ms pulse signal when the watt-hour counter

increases by the units selected.

0: 0.1 kWh units

1: 1 kWh units

2: 10 kWh units

3: 100 kWh units

4: 1000 kWh units

Default: 0

Range: 0 to 4

Table B.3 H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

0

During run

During RUN 1

Closed: A Run command is active or voltage is output.

1

Zero speed

Zero Speed

Open: Output frequency is above the minimum output frequency set in E1-09.

Closed: Output frequency is below the minimum output frequency set in E1-09.

2

Speed agree 1

Fref/Fout Agree1

Closed: Output frequency equals the speed reference (plus or minus the hysteresis

set to L4-02).

141

3

User-set speed agree 1

Fref/Set Agree 1

Closed: Output frequency and speed reference equal L4-01 (plus or minus the

hysteresis set to L4-02).

141

4

Frequency detection 1

Freq Detect 1

Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis

determined by L4-02.

5

Frequency detection 2

Freq Detect 2

Closed: Output frequency is greater than or equal to the value in L4-01 with

hysteresis determined by L4-02.

6

Drive ready

Drive Ready

Closed: Power up is complete and the drive is ready to accept a Run command.

7

DC bus undervoltage

DC Bus Undervolt

Closed: DC bus voltage is below the Uv trip level set in L2-05.

8

During baseblock

(N.O.)

BaseBlk 1

Closed: Drive has entered the baseblock state (no output voltage).

B.7 H Parameters: Multi-Function Terminals

248

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

Advertising