Hitachi L300P User Manual

Page 101

Advertising
background image

“B” Group: Fine-Tuning Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–32

Suppose the electronic thermal setting (B012) is set to 44 Amperes. The left graph below shows
the effect of the free setting torque characteristic curve. For example, at (B017) Hz, the output
current level to cause overheating in a fixed time period is reduced by a factor of (B018). The
right graph below shows the reduced trip current levels in those conditions for given trip times.

Any intelligent output terminal may be programmed to indicate a thermal warning [THM].
Parameter C061 determines the warning threshold. Please see

“Thermal Warning Signal” on

page 4–47

for more details.

Trip

time (s)

60

0.5

0

(x)

(y)

(z)

A

(x) = B018 value x 116%
(y) = B018 value x 120%
(z) = B018 value x 150%

Reduced trip current at (B017) Hz

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

B012

Level of electronic
thermal setting

Set a level between 50% and
120% of the inverter rated
current

✘ ✔

rated current for

each inverter model

%

>b012 E-THM

LEVEL 0016.5A

B212

Level of electronic
thermal setting, 2nd
motor

Set a level between 50% and
120% of the inverter rated
current

✘ ✔

rated current for

each inverter model

%

>b212 2E-THM

LEVEL 0016.5A

B013

Electronic thermal
characteristic

Select from three curves,
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting

✘ ✔

01

00

00

>b013 E-THM

CHAR CRT

B213

Electronic thermal
characteristic, 2nd
motor

Select from three curves,
option codes:
00 Reduced torque
01 Constant torque
02 V/f free-setting

✘ ✔

01

00

00

>b213 2E-THM

CHAR CRT

B015

Free setting, electronic
thermal frequency (1)

Range is 0.0 to 400.0 Hz

✘ ✔

0.

0.

0.

Hz

>b015 E-THM

F1 0000Hz

B016

Free setting, electronic
thermal current (1)

Range is 0.0 to 1000. A

✘ ✔

0.0

0.0

0.0

A

>b016 E-THM

A1 0000.0A

B017

Free setting, electronic
thermal frequency (2)

Range is 0.0 to 400.0 Hz

✘ ✔

0.

0.

0.

Hz

>b017 E-THM

F2 0000Hz

B018

Free setting, electronic
thermal current (2)

Range is 0.0 to 1000. A

✘ ✔

0.0

0.0

0.0

A

>b018 E-THM

A2 0000.0A

B019

Free setting, electronic
thermal frequency (3)

Range is 0.0 to 400.0 Hz

✘ ✔

0.

0.

0.

Hz

>b019 E-THM

F3 0000Hz

B020

Free setting, electronic
thermal current (3)

Range is 0.0 to 1000. A

✘ ✔

0.0

0.0

0.0

A

>b020 E-THM

A3 0000.0A

Advertising