Alarm signal – Hitachi L300P User Manual

Page 171

Advertising
background image

L300P Inverter

Oper

ati
ons

and Monitor

ing

4–41

Alarm Signal

The inverter alarm signal is active when a fault has
occurred and it is in the Trip Mode (refer to the
diagram at right). When the fault is cleared the
alarm signal becomes inactive.

We must make a distinction between the alarm
signal AL and the alarm relay contacts [AL0],
[AL1] and [AL2]. The signal AL is a logic
function, which you can assign to the open collec-
tor output terminals [11] to [15], or the relay
outputs. The most common (and default) use of
the relay is for AL, thus the labeling of its termi-
nals. Use an open collector output (terminals [11]
to [15]) for a low-current logic signal interface or to energize a small relay (50 mA maximum).
Use the relay output to interface to higher voltage and current devices (10 mA minimum).

Opt.

Code

Symbol

Function Name

Output

State

Description

05

AL

Alarm signal

ON

when an alarm has occurred and has not
been cleared

OFF

when no alarm has occurred since the last
clearing of alarm(s)

Valid for
outputs:

11, 12, AL0 – AL2

Required
settings:

C026, C036

Notes:
When the alarm output is set to normally

closed, a time delay of less than 2 seconds
occurs until the contact is closed when the
power is turned ON.

Terminals [11] – [15] are open collector

outputs, so the electrical specifications of
[AL] are different from the contact output
terminals [AL0], [AL1], [AL2].

When the inverter power supply is turned

OFF, the alarm signal output is valid as long
as the external control circuit has power.

This signal output has the delay time (300ms

nominal) from the fault alarm output.

The relay contact specifications are in

“Specifications of Control and Logic
Connections” on page 4–8. The contact
diagrams for different conditions are on the
next page.

Run

Stop

Trip

Fault

Fault

Alarm signal

active

RUN

STOP

RESET

STOP

RESET

Example for terminals [11C]—[11A] or
[12C]—[12A] (requires output configu-
ration—see page

3–48

):

Example for terminals [AL0], [AL1], [AL2]
(default output configuration shown—see
page

3–48

):

See I/O specs

on page

4–8

.

Inverter output
terminal circuit

AL

Inverter output terminal circuit

12C

12A

11C

11A

24VDC

L

Power
Supply

Load

AL

AL1

AL0 AL2

Relay position

shown during

normal running

(no alarm)

+

Advertising