Using Intelligent Input Terminals

Oper

ations

a

nd Moni

tor

ing

4–30

Remote Control
Up and Down
Functions

The [UP] [DWN] terminal functions can adjust the output frequency for remote control while
the motor is running. The acceleration time and deceleration time used with this function is the
same as for normal operation ACC1 and DEC1 (2ACC1,2DEC1). The input terminals operate
as follows:

• Acceleration - When the [UP] contact is turned ON, the output frequency accelerates from

the current value. When it is turned OFF, the output frequency maintains its current value.

• Deceleration - When the [DWN] contact is turned ON, the output frequency decelerates

from the current value. When it is turned OFF, the output frequency maintains its current
value.

In the graph below, the [UP] and [DWN] terminals activate while the Run command remains
ON. The output frequency responds to the [UP] and [DWN] commands.

It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals
through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter
retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the
memory and return to the original set output frequency.

Opt.

Code

Symbol

Function Name

Input

State

Description

27

UP

Remote Control
UP Function

ON

Accelerates (increases output frequency)
motor from current frequency

OFF

Output to motor operates normally

28

DWN

Remote Control
DOWN Function

ON

Decelerates (decreases output frequency)

motor from current frequency

OFF

Output to motor operates normally

29

UDC

Remote Control
Data Clear

ON

Clears the Up/down frequency memory

OFF

No effect on Up/down memory

Valid for inputs:

C001, C002, C003, C004,
C005

Required
settings:

A001 = 02
C101 = 01 (enables memory)

Notes:
This feature is available only when the

frequency command source is programmed
for operator control. Confirm A001 is set to
02.

This function is not available when [JG] is in

use.

The range of output frequency is 0 Hz to the

value in A004 (maximum frequency setting).

The Remote Control Up/Down function

varies the inverter speed by directly writing to
the F001 output frequency setting.

Output

frequency

[UP]

[FW, RV]

[DWN]

t

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

UDC

DWN

UP

Example (requires input configuration—
see page

3–43

):