Introduction

Append

ix

B

B–4

Serial Network
Parameter
Settings

Several parameter settings are necessary to configure serial communications, listed below.

For inverters on the same network, some settings must match from inverter to inverter. These
include:

• Baud rate

• Data bits

• Parity

• Stop bits

However, the node address on each inverter must be unique, used only once on the network.

Function

Code

Item

Value

Description

C070

Data command source

02

Digital operator

03

RS485 connector

04

Expansion card #1

05

Expansion card #2

C071

Baud rate

02

Loop-back test

03

2400 bps

04

4800 bps

05

9600 bps

06

19200 bps

C072

Node address

1 to 32,

FF

1 to 32 – Node or station address (unique
to each inverter or device)
FF – Automatic broadcast (to all nodes on
transmit, allowed only on certain
commands (refer to each command
description in this appendix)

C073

Data bits

07

7 bits

08

8 bits

C074

Parity

00

none

01

Even parity

02

Odd parity

C075

Stop bits

01

1 bit

02

2 bits

C078

Wait time

0 to 1000

0 to 1000 ms time that the inverter waits
to respond to network master