Using intelligent input terminals, Using intelligent input terminals 4–10, Using – Hitachi L300P User Manual

Page 140

Advertising
background image

Using Intelligent Input Terminals

Oper

ations

a

nd Moni

tor

ing

4–10

Using Intelligent Input Terminals

Intelligent terminals [1], [2], [3], [4] and [5] are identical, programmable inputs for general use.
The input circuits can use the inverter’s internal (isolated) +24V field supply (P24) to power the
inputs. The input circuits connect internally to [PLC] as a common point. To use the internal
supply to power the inputs, use the jumper as shown. Remove the jumper to use an external
supply, or to interface to a PLC system (or other) that has solid state outputs. If you use an
external supply or PLC system, its power return must connect to the [PLC] terminal on the
inverter to complete the input circuit.

The following four input configurations are available to interface the inverter inputs to switches
or the outputs of another system, such as a PLC.

5

3

1

4

2

Input circuits

+ –

24VDC

common

Jumpered for sinking inputs

(default for –xFE2 models)

Sinking inputs,
internal supply

L300P inverter

5

3

1

PLC

CM1

4

2

Input circuits

+ –

24VDC

common

L300P inverter

5

3

1

4

2

Input circuits

+ –

24VDC

common

External

power supply

L300P inverter

5

3

1

4

2

Input circuits

+ –

24VDC

common

L300P inverter

Sourcing inputs,

internal supply

Sinking inputs,

external supply

Sourcing inputs,

external supply

Jumpered for sourcing inputs

(default for –xFU2/–FR models)

External

power supply

P24

PLC

CM1

P24

PLC

CM1

P24

PLC

CM1

P24

+

+

Advertising