Hitachi L300P User Manual

Page 56

Advertising
background image

L300P Inverter

In

v

e

rt

er Mounting

and In

stallati

on

2–17

Terminal dimensions and torque specs, continued...

Note 1: The recommended ring lug connector listing consists of wire size – screw size

format. The wire sizes are in AWG or mm

2

format. For AWG wire sizes, bolt sizes

for the ring lug centers are: #10, #12, 1/4”, 5/16”, and 1/2”. For metric wire sizes, bolt
sizes for the ring lug centers are: 6 = 6M, 8 = 8M, 10 = 10M.

Input

Voltage

Motor

Output

400V

Inverter

Models,

L300P

Length

of

power

wiring

Screw size

of terminal

Ring Lug Connector *1

Torque

HP

kW

(AWG–bolt)

(mm

2

–bolt)

ft-lbs

N-m

400V

2

1.5

–015HFU2, HFE2

M4

14–10

2–4

1.1

1.5

3

2.2

–022HFU2, HFE2

M4

14–10

2–4

1.1

1.5

5

4.0

–040HFU2, HFE2

M4

14–10

2–4

1.1

1.5

7.5

5.5

–050HFU2, HFE2

M5

14–12

2–5

1.8

2.5

10

7.5

–075HFU2, HFE2

M5

10–12

3.5–5

1.8

2.5

15

11

-110HFU2, HFE2

M6

8–1/4

5.5–6

3.6

4.9

20

15

-150HFU2, HFE2

M6

6–1/4

8–6

3.6

4.9

25

18.5

-185HFU2, HFE2

M6

6–1/4

14–6

3.6

4.9

30

22

-220HFU2, HFE2

M6

4–1/4

14–6

3.6

4.9

40

30

-300HFU2, HFE2

M6

3–1/4

22–6

3.6

4.9

50

37

-370HFU2, HFE2

M6

4–1/4

14–6

3.6

4.9

60

45

-450HFU2, HFE2

M8

1–5/16

38–8

6.5

8.8

75

55

-550HFU2, HFE2

M8

3–5/16

22–8

6.5

8.8

100

75

-750HFU2, HFE2

M8

2–5/16

30–8

6.5

8.8

125

90

-900HFU2, HFE2

M10

1–1/2

38–10

10.1

13.7

150

110

-1100HFU2, HFE2

M10

1/0–1/2

50–10

10.1

13.7

175

132

-1320HFU2, HFE2

M10

2/0–1/2

60–10

10.1

13.7

Advertising