Follow the steps to implement the wiring change shown in the previous diagram.

1. Remove the 2-wire jumper J51 (terminals [R0] and [T0] to connector J51).
2. Procure several inches of multi-strand 20 AWG (0.5mm

2

) or slightly heavier wire.

3. Connect a wire to terminal [R0] that is long enough to connect to terminal [P] (do not

connect to [P] yet).

4. Connect a wire to terminal [T0] that is long enough to connect to terminal [N] (do not

connect to [N] yet).

5. Remove the ferrite filter from the original jumper wire and then slide it onto the new wires

connecting to terminals [R0] and [T0]. (Be sure to save the original jumper in a safe place.)

6. Connect the wire from [R0] to [P], and connect the wire from [T0] to [N] as shown.

More information on power loss related alarm functions, see

“Instantaneous Power Failure /

Under-voltage Signal” on page 4–43

.