Software Lock
Mode

The software lock function keeps personnel from accidentally changing parameters in the
inverter memory. Use B031 to select from various protection levels.

The table below lists all combinations of B031 option codes and the
ON/OFF state of the [SFT] input. Each Check

✔ or Ex ✘ indicates

whether the corresponding parameter(s) can be edited. The Standard
Parameters column below lists Low and High level access for some
lock modes. These refer to the parameter tables throughout this
chapter, each of which includes a column titled Run Mode Edit as
shown to the right. The two marks (Check

✔ or Ex ✘) under the “Lo

Hi” subtitle indicate whether Low-level and/or High-level access
applies to each parameter as defined in the table below. In some lock modes, you can edit only
F001 and the Multi-speed parameter group that includes A020, A220, A320, A021–A035, and
A038 (Jog). However, it does not include A019, Multi-speed operation selection. The editing
access to B031 itself is unique, and is specified in the right-most two columns below.

NOTE: Since the software lock function B031 is always accessible when the motor is stopped,
this feature is not the same as password protection used in other industrial control devices.

NOTE: To disable parameter editing when using B031 lock modes 00 and 01, assign the [SFT]
function to one of the intelligent input terminals. See

“Software Lock” on page 4–24

.

B031
Lock

Mode

[SFT]

Intelligent

Input

Standard Parameters

F001 and

Multi-speed

B031

Stop

Run

Stop or Run

Stop

Run

00

OFF

Low-level

ON

01

OFF

Low-level

ON

02

(ignored)

03

(ignored)

10

(ignored)

High-level

Run

Mode

Edit

Lo Hi

✘ ✔

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

B031

Software lock mode
selection

Prevents parameter changes
in five options:
00 Low-level access, [SFT]

input blocks all edits

01 Low-level access, [SFT]

input blocks edits
(except F001 and Multi-
speed parameters)

02 No access to edits
03 No access to edits except

F001 and Multi-speed
parameters

10 High-level access,

including B031

✘ ✔

01

01

01

>b031 S-LOCK

Mode MD1