L300P Inverter

Appendix B

B–13

Command – 07

The 07 command sets a parameter value equal to the value specified in the transmission.The
frame format of command 07 follows the diagram and specification table.

Note that the parameter F001, the output frequency, can be set more directly with host
command 01 instead of with this command. Use the codes in the following table for setting
parameters associated with H003 and H203.

Element

Description

Size

Value

STX

Control code (STart of TeXt)

1 byte

STX (0x02)

Node

Node (station) address of inverter

2 bytes 01 to 32, and FF (broadcast to all

nodes)

Command

Transmission command

2 bytes 07

Parameter

Function code of parameter

4 bytes F002..., A001..., B001..., C001...,

H003..., P001...

Data

Transmission data

8 bytes Value of parameter times ten as

ASCII char. code, except for
H003 and H203 (see table below)

BCC

Block check sum code

2 bytes Exclusive OR of Node,

Command, and Data

[CR]

Control code (carriage return)

1 byte

[CR] (0x0D)

Code Data

00

01

02

03

04

05

06

07

08

09

10

U.S. mode (B85=00, 02)

0.2 kW

0.4

0.75

1.5

2.,2

3.7

EU mode (B85=01)

0.2 kW

0.37

0.55

0.75

1.1

1.5

2.2

3.0

4.0

Code Data

11

12

13

14

15

16

17

18

19

20

21

U.S. mode (B85=00, 02)

5.5 kW

7.5

11

15

18.5

22

30

37

45

55

75

EU mode (B85=01)

5.5 kW

7.5

11

15

18.5

22

30

37

45

55

75

STX Node

Command

Data

BCC [CR]

Frame format

Parameter