Frequency Arrival
Signals

The Frequency Arrival group of outputs help coordinate external systems with the current
velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output
frequency arrives at the standard set frequency (parameter F001). Outputs [FA2] through [FA5]
provide variations on this function for increased flexibility, relying on two programmable accel/
decel thresholds. For example, you can have an output turn ON at one frequency during accel-
eration, and have it turn OFF at a different frequency during deceleration. All transitions have
hysteresis to avoid output chatter if the output frequency is near one of the thresholds.

Opt.

Code

Symbol

Function Name

Output

State

Description

01

FA1

Frequency arrival
type 1 – constant
speed

ON

when output to motor is at the standard set
frequency F001

OFF

when output to motor is not at the set
frequency F001

02

FA2

Frequency arrival
type 2 – over-
frequency

ON

when output to motor is at or above the FA
threshold 1(C042) during accel

OFF

when the output to motor is below the FA
threshold 1 (C043) during decel

06

FA3

Frequency arrival
type 3 – at
frequency

ON

when output to motor is at the FA thresh-
old 1 (C042) during accel, or at C043
during decel

OFF

when the output to motor is not at either
the FA threshold 1 (C042) during accel or
at C043 during decel

Valid for
outputs:

11, 12, AL0 – AL2

Required
settings:

F001, for FA1
C042 & C043, for FA2 & FA3

Notes:
For most applications you will need to use

only one or two of the frequency arrival type
outputs (see example). However, it is possible
assign all three output terminals to output
functions [FA1] through [FA3].

For each frequency arrival threshold, the

output anticipates the threshold (turns ON
early) by an amount equal to 1% of the
maximum frequency set for the inverter.

The output turns OFF as the output frequency

moves away from the threshold, delayed by
an amount equal to 2% of the max. frequency.

FA2

FA1

See I/O specs on page

4–8

.

Inverter output terminal circuit

12C

12A

11C

11A

24VDC

L

L

Example (requires output configuration—
see page

3–48

):

+

Advertising