Ul® cautions, warnings, and instructions, Terminal tightening torque and wire size, Cautions, warnings, and instructions – Hitachi L300P User Manual

Page 13

Advertising
background image

xii

UL

®

Cautions, Warnings, and Instructions

Wiring Warnings
for Electrical
Practices and
Wire Sizes

The Cautions, Warnings, and instructions in this section summarize the procedures necessary to
ensure an inverter installation complies with Underwriters Laboratories

®

guidelines.

WARNING: “Use 60/75°C Cu wire only” or equivalent.

WARNING: “Open Type Equipment.” For models L300P–900H to L300P–1320H.

WARNING: “Suitable for use on a circuit capable of delivering not more than 10,000 rms
symmetrical amperes, 240 V maximum.” For models with suffix L.

WARNING: “Suitable for use on a circuit capable of delivering not more than 10,000 rms
symmetrical amperes, 480 V maximum.” For models with suffix H.

Terminal Tighten-
ing Torque and
Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the table
below.

TIP: AWG = American Wire Gauge. Smaller numbers represent increasing wire thickness.
kcmil = 1,000 circular mils, a measure of wire cross-sectional area
mm

2

= square millimeters, a measure of wire cross-sectional area

Input

Voltage

Motor

Output

Inverter Models,

L300P

Wire Size Range (AWG)

Torque

HP

kW

ft-lbs

N-m

200V

2

1.5

-015LFU2

14

1.1

1.5

3

2.2

-022LFU2

14

1.1

1.5

5

3.7

-037LFU2

10

1.1

1.5

7.5

5.5

-055LFU2

8

1.8

2.5

10

7.5

-075LFU2

6

1.8

2.5

15

11

-110LFU2

4

3.6

4.9

20

15

-150LFU2

2

3.6

4.9

25

18.5

-185LFU2

4 || 4 AWG

3.6

4.9

30

22

-220LFU2

1/0

6.5

8.8

40

30

-300LFU2

2 || 2 AWG

6.5

8.8

50

37

-370LFU2

1 || 1AWG

6.5

8.8

60

45

-450LFU2

1 || 1 AWG (75°C)

10.1

13.7

75

55

-550LFU2

2/0 || 2/0 AWG

10.1

13.7

100

75

-750LFU2

3/0 || 3/0 AWG

10.1

13.7