“B” Group: Fine-Tuning Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–34

NOTE: Two sets of overload restriction parameters are available. The set that is in use may be
selected by means of an intelligent input terminal (see

“Overload Restriction” on page 4–32

).

B025

Overload restriction
setting (2)

Sets the level for overload
restriction (2), between 50%
and 150% of the rated
current of the inverter,
setting resolution is 1% of
rated current

✘ ✔

rated current times

1.20

A

>b025 OLOAD

2LEVEL 0024.8A

B026

Deceleration rate at
overload restriction (2)

Sets the deceleration rate (2)
when inverter detects
overload, range is 0.1 to
30.0, resolution is 0.1.

✘ ✔ 1.00 1.00 1.00

sec.

>b026 OLOAD

2CONST 01.00

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)