Force operation from digital operator – Hitachi L300P User Manual

Page 161

Advertising
background image

L300P Inverter

Oper

ati
ons

and Monitor

ing

4–31

Force Operation
from Digital
Operator

This function permits a digital operator interface to override the Run command source setting
(A002) when it is configured for a source other than the operator interface. When the [OPE]
terminal is ON and the operator interface gives a Run command, the inverter uses the standard
output frequency settings to operate the motor.

Opt.

Code

Symbol

Function Name

Input

State

Description

31

OPE

Force Operation
from Digital
Operator

ON

Forces the operator interface Run
command to over-ride commands from
input terminals (such as [FW], [RV]).

OFF

Run command operates normally, as
configured by A002

Valid for inputs:

C001, C002, C003, C004,
C005

Required
settings:

A001
A002 (set not equal to 02)

Notes:
When changing the [OPE] state during Run

Mode (inverter is driving the motor), the
inverter will stop the motor before the new
[OPE] state takes effect.

If the [OPE] input turns ON and the digital

operator gives a Run command while the
inverter is already running, the inverter stops
the motor. Then the digital operator can
control the motor.

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

OPE

Example (requires input configuration—
see page

3–43

):