L300P Inverter

Appendix B

B–9

The data in the receive frame contains 8-byte values for 13 items, listed in the table below:

The eight bytes for intelligent input or intelligent output data have a bit set in the data field for
each I/O point that is ON, according to the following table:

No.

Monitor Item

Units

Multiplier

1

Output frequency

Hz

100

2

Output current

A

10

3

Direction of rotation

4

PID feedback monitor

%

100

5

Intelligent input monitor

6

Intelligent output monitor

7

Frequency converting monitor

100

8

Output torque monitor

%

1

9

Output voltage monitor

V

10

10

Electric power monitor

kW

10

11

Reserved

12

Run Mode time monitor

hours

1

13

Power ON time monitor

hours

1

Terminal

Monitor Item

Data

[FW]

Forward input

00000001

[1]

Input 1

00000002

[2]

Input 2

00000004

[3]

Input 3

00000008

[4]

Input 4

00000010

[5]

Input 5

00000020

[6]

Input 6

00000040

[7]

Input 7

00000080

[8]

Input 8

00000100

[AL]

Alarm relay

00000001

[11]

Output 1

00000002

[12]

Output 2

00000004

[13]

Output 3

00000008

[14]

Output 4

00000010

[15]

Output 5

00000020