Run signal – Hitachi L300P User Manual

Page 166

Advertising
background image

Using Intelligent Output Terminals

Oper

ations

a

nd Moni

tor

ing

4–36

Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is
in Run Mode. The output logic is active
low, and is the open collector type (switch
to common).

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to
prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s
output transistor.

Opt.

Code

Symbol

Function Name

Output

State

Description

00

RUN

Run signal

ON

when inverter is in Run Mode

OFF

when inverter is in Stop Mode

Valid for
outputs:

11, 12, AL0 – AL2

Required
settings:

(none)

Notes:
The inverter outputs the [RUN] signal

whenever the inverter output exceeds the start
frequency specified by parameter B082. The
start frequency is the initial inverter output
frequency when it turns ON.

[FW, RV]

Motor

speed

Run

Signal

start freq.

B82

ON

t

RUN

See I/O specs on page

4–8

.

Inverter output terminal circuit

12C

12A

11C

11A

24VDC

L

Example: (default output configuration
shown—see page

3–48

):

+