Overload
Restriction

If the inverter’s output current exceeds a
preset current level you specify during
acceleration or constant speed, the
overload restriction feature automati-
cally reduces the output frequency to
restrict the overload. This feature does
not generate an alarm or trip event. You
can instruct the inverter to apply
overload restriction only during
constant speed, thus allowing higher
currents for acceleration. Or, you may
use the same threshold for both acceler-
ation and constant speed. In the case of
controlled deceleration, the inverter monitors both output current and DC bus voltage. The
inverter will increase output frequency to try to avoid a trip due to over-current or over-voltage
(due to regeneration).

When the inverter detects an overload, it must decelerate the motor to reduce the current until it
is less than the threshold. You can choose the rate of deceleration that the inverter uses to lower
the output current.

0

Motor

Current

V

Output

Frequency

restriction area

B023

B022

t

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

B021

Overload restriction
operation mode

Select the operating mode
during overload conditions,
three options, option codes:
00 Disabled
01 Enabled for acceleration

and constant speed

02 Enabled for constant

speed only

03 Enabled for accel, decel,

and constant speed

✘ ✔

01

01

01

>b021 OLOAD

1MODE ON

B022

Overload restriction
setting

Sets the level for overload
restriction, between 50%
and 150% of the rated
current of the inverter,
setting resolution is 1% of
rated current

✘ ✔

rated

cur-
rent

times

1.20

rated

cur-
rent

times

1.10

rated

cur-
rent

times

1.20

A

>b022 OLOAD

1LEVEL 0024.8A

B023

Deceleration rate at
overload restriction

Sets the deceleration rate
when inverter detects
overload, range is 0.1 to
30.0, resolution is 0.1.

✘ ✔ 1.00 15.0 1.00

sec.

>b023 OLOAD

1CONST 01.00

B024

Overload restriction
operation mode (2)

Select the operating mode
motor during overload
conditions, three options,
option codes:
00 Disabled
01 Enabled for acceleration

and constant speed

02 Enabled for constant

speed only

03 Enabled for accel, decel,

and constant speed

✘ ✔

01