External signal for dc braking, Exter, For mo – Hitachi L300P User Manual

Page 146

Advertising
background image

Using Intelligent Input Terminals

Oper

ations

a

nd Moni

tor

ing

4–16

External Signal
for DC Braking

When the terminal [DB] is turned ON, the
DC braking [DB] feature is enabled. Set the
following parameters when the external DC
braking terminal is to be used:

• A053 – DC braking delay time setting.

The range 0.0 to 5.0 seconds.

• A054 – DC braking force setting. The

range is 0 to 100%.

The scenarios to the right help show how
DC braking works in various situations.

1. Scenario 1 – The [FW] Run or [RV]

Run terminal is ON. When the [DB]
terminal turns ON, DC braking is
applied. When the [DB] terminal turns
OFF again, the inverter output ramps to
the previous frequency.

2. Scenario 2 – The Run command is

applied from the operator keypad. When
the [DB] terminal turns ON, DC braking
is applied. When the [DB] terminal
turns OFF again, the inverter output
remains OFF.

3. Scenario 3 – The Run command is

applied from the operator keypad. When
the [DB] terminal turns ON, DC braking
is applied after the delay time set by
A053 expires. The motor is in a free-
running (coasting) condition during this
delay time. When the [DB] terminal
turns OFF again, the inverter output
remains OFF.

Opt.

Code

Symbol

Function Name

Input

State

Description

07

DB

External Signal for
DC Injection
Braking

ON

applies DC injection braking during
deceleration

OFF

does not apply DC injection braking
during deceleration

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

A053, A054

Notes:
Do not use the [DB] input continuously or for

a long time when the DC braking force
setting A054 is high (depends on the motor
application).

Do not use the [DB] feature for continuous or

high duty cycle as a holding brake. The [DB]
input is designed to improve stopping perfor-
mance. Use a mechanical brake for holding a
stop position.

Output

frequency

[FW, RV]

[DB]

Scenario 1

Output

frequency

Run command

from operator)

Scenario 2

Output

frequency

Scenario 3

[DB]

delay

Run command

from operator)

[DB]

A053

t

t

t

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

DB

Example (requires input configuration—
see page

3–43

):