Run Enable for
FW/RV (–xFU2
models only)

The Run Enable for FW/RV input provides a way to enable or disable the [FW] and [RV] input
terminals in real time, including a Run command from an operator keypad. This is useful for
applications that require a logic type safety interlock for FWD Run or REV Run commands.

The Run Enable for FW/RV function is assigned to an intelligent input terminal using option
code 49. When assigned, the output frequency operates as a logical AND of the Run Enable for
FW/RV input and a [FW], [RV], or keypad Run command input. The Run Enable for RV input
is level-sensitive, as shown in the timing diagram below. The leading edges (OFF-to-ON transi-
tions) of the Run Enable for RV input and the [FW] or [RV] input can occur in any order. The
output frequency follows the logical AND of these inputs.

Opt.

Code

Symbol

Function Name

Input

State

Description

49

ROK

Run Enable for
FW/RV

ON

[FW] and [RV] inputs and operator Run
key press operate normally

OFF

[FW] and [RV] inputs and operator Run
key press are ignored; inverter output
remains OFF

Valid for inputs:

C001, C002, C003, C004,
C005

Required
settings:

(none)

Notes:
This function is only available on –xFU2

models.

When the Run Enable for FW/RV function is

not assigned to any intelligent input terminal,
the FWD Run and REV Run commands
operate normally (directly control the output
frequency).

To ensure safe inverter operation in

networked applications, you cannot change an
intelligent terminal assignment to/from
[ROK] (option code 49) via the network.
However, you can still read an [ROK] input
assignment over the network.

[F/R] terminal

[ROK] terminal

Output
frequency

t

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

ROK

Example (requires input configuration—
see page

3–43

):