External Trip

When the terminal [EXT] is turned ON, the inverter enters the trip state, indicates error code
E12, and stops the output. This is a general purpose interrupt type feature, and the meaning of
the error depends on what you connect to the [EXT] terminal. Even if [EXT] is turned OFF, the
inverter remains in the trip state. You must reset the inverter or cycle power to clear the error,
returning the inverter to the Stop Mode.

In the graph below, the [EXT] input turns ON during normal Run Mode operation. The inverter
lets the motor free-run to a stop, and the alarm output turns ON immediately. When the
operator initiates a Reset command, the alarm and error are cleared. When the Reset is turned
OFF, the motor begins rotation since the Run command is already active.

Opt.

Code

Symbol

Function Name

Input

State

Description

12

EXT

External Trip

ON

When assigned input transitions OFF to
ON, inverter latches trip event and
displays E12

OFF

No trip event for ON to OFF, any recorded
trip events remain in history until Reset

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

(none)

Notes:
If the USP (Unattended Start Protection)

feature is in use, the inverter will not automat-
ically restart after cancelling the EXT trip
event. In that case, it must receive either
another Run command (OFF-to-ON transi-
tion), a keypad Reset command, or an [RS]
intelligent terminal input signal.

free run

[EXT]

[FW, RV]

[RS]

Motor revolution speed

Alarm output terminal

t

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

EXT

Example (requires input configuration—
see page

3–43

):