The miscellaneous settings include scaling factors, initialization modes, and others. This
section covers some of the most important settings you may need to configure.

Function Code Display Restriction – The inverter has the (optional) capability to suppress the
display and editing of certain parameters. Use B037 to select the display options. The purpose
of this feature is to hide particular secondary parameters that become unused or not applicable
based on more fundamental parameter settings. For example, setting A001 = 01 configures the
inverter to get its frequency command from the front keypad potentiometer. In this case, the
inverter will not use the analog inputs nor their adjustment parameters for an external frequency
command.

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

B034

Run/power-on warning
time

Range is 0 to 65,530 hours

✘ ✔

0.

0.

0.

hrs.

>b034 TIME

WARN 00000

B035

Rotational direction
restriction

Three option codes:
00 Enable for both dir.
01 Enable for forward only
02 Enable for reverse only

✘ ✘

00

00

00

>b035 LIMIT

F/R FREE

B036

Reduced voltage start
selection

Seven option codes:
00 Short
01, 02, 03, 04, 05 (middle)
06 Long

✘ ✔

06

06

06

>b036 RVS

ADJUST 06

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

B037

Function code display
restriction

Three option codes:
00 Display all
01 Display only utilized

functions (see table
below)

02 Display user-selected

functions only (con-
figure with U01 to U12)

✘ ✔

00

00

00

>b037 DISP

Mode ALL