Communications protocol, Introduction to command list, Communications protocol b–5 – Hitachi L300P User Manual

Page 231

Advertising
background image

L300P Inverter

Appendix B

B–5

Communications Protocol

Introduction to
Command List

The network master sends a frame to initiate
communications with a slave, as shown in the
figure to the right. After the set waiting time
(per parameter C078, the inverter responds.

The following table lists the commands, single-character codes sent to a particular device on
the network.

NOTE: Use of command 08 – set inverter parameters to default values first requires setting the
initialization mode parameter B084 to 01 (initializes parameters only) or 02 (initializes param-
eters and clears the trip history).

Command

Code

Description

User-selectable

00

Forward / Reverse / Stop command

01

Setting of frequency in standard profile

02

Setting of intelligent terminal state

03

Read all monitor data (block read)

04

Read inverter status

05

Read trip history

06

Read a single parameter value

07

Write a single parameter value

08

Set inverter parameters to default values

09

Verifies that the requested setting can be
written to EEPROM.

0A

Writes a parameter value to EEPROM

0B

Requests the recalculation of internal constant

Host

(master)

wait

time

frame

Inverter

(slave)

frame