Output terminal configuration – Hitachi L300P User Manual

Page 117

Advertising
background image

“C” Group: Intelligent Terminal Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–48

Output Terminal
Configuration

The inverter provides configuration for logic (discrete) and analog outputs, shown in the table
below.

The output logic convention is programmable for terminals [11], [12], and the alarm relay
terminals. The open-collector output terminals [11] and [12] default to normally open (active
low), but you can select normally closed (active high) for the terminals in order to invert the
sense of the logic. You can invert the logical sense of the alarm relay output as well.

“C” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

C021

Terminal [11] function

12 programmable

functions

(13 functions for

–xFE2/–xFU2

models) available for

logic (discrete)

outputs (see next

section)

✘ ✔

01

[FA1]

01

[FA1]

01

[FA1]

>C021 OUT-TM

11 FA1

C022

Terminal [12] function

✘ ✔

00

[RUN]

00

[RUN]

00

[RUN]

>C022 OUT-TM

12 RUN

C026

Alarm relay terminal
function

✘ ✔

05

[AL]

05

[AL]

05

[AL]

>C026 OUT-TM

AL AL

C027

[FM] signal selection

7 programmable

functions available

for analog outputs

(see after next

section)

✘ ✔

00

output

freq.

00

output

freq.

00

output

freq.

>C027 FM-MONITOR

KIND A-F

C028

[AM] signal selection

✘ ✔

00

output

freq.

00

output

freq.

00

output

freq.

>C028 AM-MONITOR

KIND A-F

C029

[AMI] signal selection

✘ ✔

00

output

freq.

00

output

freq.

00

output

freq.

>C029 AMI-MON

KIND A-F

“C” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

C031

Terminal [11] active
state

Select logic convention,
two option codes:
00 normally open N.O.
01 normally closed N.C.

✘ ✔

00

00

00

>C031 OUT-TM

O/C-11 NO

C032

Terminal [12] active
state

✘ ✔

00

00

00

>C032 OUT-TM

O/C-12 NO

C036

Alarm relay terminal
active state

✘ ✔

01

01

01

>C036 OUT-TM

O/C-AL NC