Jogging command – Hitachi L300P User Manual

Page 145

Advertising
background image

L300P Inverter

Oper

ati
ons

and Monitor

ing

4–15

Jogging
Command

The Jog input [JG] is used to command the
motor to rotate slowly in small increments
for manual operation. The speed is limited
to 10 Hz. The frequency for the jogging
operation is set by parameter A038. Jogging
does not use an acceleration ramp. There-
fore setting the jogging frequency A038 too
high will cause inverter tripping.

A jog command may arrive while the motor
is running. You can program the inverter to
either ignore or respond to a jog command
in this case by using function A039. The
type of deceleration used to end a motor jog
is also selectable by programming function A039. Six jog mode options are defined below:

In the left example diagram below, the Jog command is ignored. In the right example diagram,
a jog command interrupts a Run mode operation. However, if the Jog command turns ON
before the [FW] or [RV] terminal turns ON, the inverter output turns OFF.

Jogging During Motor Operation

Jog Deceleration Method

Disabled, A039=

Enabled, A039=

00

03

Free-run stop (coasting)

01

04

Deceleration (normal level) and stop

02

05

Use DC braking and stop

Opt.

Code

Symbol

Function Name

Input

State

Description

06

JG

Jogging

ON

Enters Jog Mode if enabled (see above)

OFF

Jog is OFF

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

A002= 01, A038 > B082,
A038 > 0, A039=00 to 05

Notes:
Jogging is not performed when the value of

A038 jogging frequency is smaller than the
start frequency B082 or the

value is 0 Hz.

Be sure to turn ON [FW] or [RV] after the

[JG] input turns ON for a jog operation.

When setting A039 to 02 or 05, you must also

set the DC braking parameters.

[JG]

[FW]

Jog decel type

[RV]

Output

frequency

A038

A039

t

t

[JG]

[FW]

Output

frequency

A039=00, 01, 02

Decelerating stop (00) shown

t

[JG]

[FW]

Output

frequency

A039=03, 04, 05

Free-run stop (05) shown

A038

A038

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

JG

Example (requires input configuration—
see page

3–43

):