“B” Group: Fine-Tuning Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–42

Free-setting
V/f Pattern

The free-setting V/f inverter mode of operation uses voltage and frequency parameter pairs to
define seven points on a V/f graph. This provides a way to define a multi-segment V/f curve
that best suits your application.

The frequency settings do require that F1

≤ F2 ≤ F3 ≤ F4 ≤ F5 ≤ F6 ≤ F7; their values must have

this ascending order relationship. To satisfy this criterion during initial parameter editing, set
F7 (B012) and work backwards when setting these values, since the defaults are all 0 Hz.
However, the voltages V1 to V7 may either increase or decrease from one to the next. There-
fore, you may set these parameters in any order.

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

B100

Free-setting V/f
frequency (1)

V/f point 1, frequency
coordinate

✘ ✘

0.

0.

0.

Hz

>b101 FREE-V/F

V1 000.0V

B101

Free-setting V/f
voltage (1)

V.F point 1, voltage coordi-
nate

✘ ✘

0.0

0.0

0.0

V

>b102 FREE-V/F

F1 0000Hz

B102

Free-setting V/f
frequency (2)

V/f point 2, frequency
coordinate

✘ ✘

0.

0.

0.

Hz

>b103 FREE-V/F

V2 000.0V

B103

Free-setting V/f
voltage (2)

V.F point 2, voltage coordi-
nate

✘ ✘

0.0

0.0

0.0

V

>b104 FREE-V/F

F2 0000Hz

B104

Free-setting V/f
frequency (3)

V/f point 3, frequency
coordinate

✘ ✘

0.

0.

0.

Hz

>b105 FREE-V/F

V3 000.0V

B105

Free-setting V/f
voltage (3)

V.F point 3, voltage coordi-
nate

✘ ✘

0.0

0.0

0.0

V

>b106 FREE-V/F

F3 0000Hz

B106

Free-setting V/f
frequency (4)

V/f point 4, frequency
coordinate

✘ ✘

0.

0.

0.

Hz

>b107 FREE-V/F

V4 000.0V

B107

Free-setting V/f
voltage (4)

V.F point 4, voltage coordi-
nate

✘ ✘

0.0

0.0

0.0

V

>b108 FREE-V/F

F4 0000Hz

B108

Free-setting V/f
frequency (5)

V/f point 5, frequency
coordinate

✘ ✘

0.

0.

0.

Hz

>b109 FREE-V/F

V5 000.0V

B109

Free-setting V/f
voltage (5)

V.F point 5, voltage coordi-
nate

✘ ✘

0.0

0.0

0.0

V

>b110 FREE-V/F

F5 0000Hz

B110

Free-setting V/f
frequency (6)

V/f point 6, frequency
coordinate

✘ ✘

0.

0.

0.

Hz

>b111 FREE-V/F

V6 000.0V

B111

Free-setting V/f
voltage (6)

V.F point 6, voltage coordi-
nate

✘ ✘

0.0

0.0

0.0

V

>b112 FREE-V/F

F6 0000Hz

B112

Free-setting V/f
frequency (7)

V/f point 7, frequency
coordinate

✘ ✘

0.

0.

0.

Hz

>b113 FREE-V/F

V7 000.0V

B113

Free-setting V/f
voltage (7)

V.F point 7, voltage coordi-
nate

✘ ✘

0.0

0.0

0.0

V

>b114 FREE-V/F

F7 0000Hz