Frequency- related functions – Hitachi L300P User Manual

Page 88

Advertising
background image

L300P Inverter

Configur

ing Dr

iv

e

P

a

ra

met

e

rs

3–19

Frequency-
related Functions

Frequency Limits – Upper and lower
limits can be imposed on the inverter
output frequency. These limits will apply
regardless of the source of the speed
reference. You can configure the lower
frequency limit to be greater than zero as
shown in the graph to the right. The upper
limit must not exceed the rating of the
motor or capability of the machinery.

Jump Frequencies – Some motors or machines exhibit resonances at particular speed(s),
which can be destructive for prolonged running at those speeds. The inverter has up to three
jump frequencies as shown in the graph. The hysteresis around the jump frequencies causes the
inverter output to skip around the sensitive frequency values.

Output frequency

Upper

limit

Frequency command

Lower

limit

Settable

range

A061

A062

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

A061 Frequency upper limit

setting

Sets a limit on output
frequency less than the
maximum frequency (A004)
Range is 0.50 to 400.0 Hz
0.00 setting is disabled
>0.10 setting is enabled

✘ ✔ 0.00 0.00 0.00

Hz

>A061 LIMIT

HIGH 0000.00Hz

A261 Frequency upper limit

setting, 2nd motor

Sets a limit on output
frequency less than the
maximum frequency (A004)
Range is 0.50 to 400.0 Hz
0.00 setting is disabled
>0.10 setting is enabled

✘ ✔ 0.00 0.00 0.00

Hz

>A261 2LIMIT

HIGH 0000.00Hz

A062 Frequency lower limit

setting

Sets a limit on output
frequency greater than zero
Range is 0.50 to 400.0 Hz
0.00 setting is disabled
>0.1 setting is enabled

✘ ✔ 0.00 0.00 0.00

Hz

>A062 LIMIT

LOW 0000.00Hz

A262 Frequency lower limit

setting, 2nd motor

Sets a limit on output
frequency greater than zero
Range is 0.50 to 400.0 Hz
0.00 setting is disabled
>0.10 setting is enabled

✘ ✔ 0.00 0.00 0.00

Hz

>A262 2LIMIT

LOW 0000.00Hz

Frequency command

Jump frequencies

Output

frequency

Hysteresis values

A067

A065

A063

A064

A064

A066

A066

A068

A068

Advertising