“C” Group: Intelligent Terminal Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–46

13

USP

Unattended Start
Protection

ON

ON powerup, the inverter will not resume a Run
command (mostly used in the US)

OFF

ON powerup, the inverter will resume a RUN
command that was active before power loss

14

CS

Commercial Power
Source

ON

OFF-to-ON transition signals the inverter that the
motor is already running at powerup (via bypass),
thus suppressing the inverter’s motor output in Run
Mode

OFF

ON-to-OFF transition signals the inverter to apply a
time delay (B003), frequency match its output to
existing motor speed, and resume normal Run Mode
operation

15

SFT

Software Lock

ON

The keypad and remote programming devices are
prevented from changing parameters

OFF

The parameters may be edited and stored

16

AT

Analog Input Voltage/
current Select

ON

Terminal [OI] is enabled for current input (uses
terminal [L] for signal return)

OFF

Terminal [O] is enabled for voltage input (uses
terminal [L] for signal return)

18

RS

Reset Inverter

ON

The trip condition is reset, the motor output is turned
OFF, and powerup reset is asserted

OFF

Normal power-on operation

20

STA

START
(3-wire interface)

ON

Starts the motor rotation

OFF

No change to present motor status

21

STP

STOP
(3-wire interface)

ON

Stops the motor rotation

OFF

No change to present motor status

22

F/R

FWD, REV
(3-wire interface)

ON

Selects the direction of motor rotation: ON = FWD.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction.

OFF

Selects the direction of motor rotation: OFF =REV.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction.

23

PID

PID Disable

ON

Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active
(A071=1).

OFF

Has no effect on PID loop operation, which operates
normally if PID Enable is active (A071 = 1).

24

PIDC

PID Reset

ON

Resets the PID loop controller. The main conse-
quence is that the integrator sum is forced to zero.

OFF

No effect on PID loop controller

27

UP

Remote Control
UP Function (motor-
ized speed pot.)

ON

Accelerates (increases output frequency) motor from
current frequency

OFF

No change to output frequency

Input Function Summary Table

Option

Code

Terminal

Symbol

Function Name

Description