“A” Group: Standard Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–22

Automatic
Voltage
Regulation (AVR)
Function

The automatic voltage regulation (AVR) feature keeps the inverter output voltage at a
relatively constant amplitude during power input fluctuations. This can be useful if the installa-
tion is subject to input voltage disturbances. However, the inverter cannot boost its motor
output to a voltage higher than the power input voltage. If you enable this feature, be sure to
select the proper voltage class setting for your motor.

Energy Savings
Mode

This function allows the inverter to deliver the minimum power necessary to maintain speed at
any given frequency. This works best when driving variable torque characteristic loads such as
fans and pumps. Parameter A085 enables this function and A086 controls the degree of its
effect. A setting of 0.0 yields slow response but high accuracy, while a setting of 100 will yield
a fast response with lower accuracy.

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

A081 AVR function select

Automatic (output) voltage
regulation, selects from
three type of AVR functions,
three option codes:
00 AVR enabled
01 AVR disabled
02 AVR enabled except

during deceleration

✘ ✘

00

00

02

>A081 AVR

MODE DOFF

A082 AVR voltage select

200V class inverter settings:

200/215/220/230/240

400V class inverter settings:

380/400/415/440/460/
480

✘ ✘

230/

400

230/

460

200/

400

V

>A082 AVR

AC 230

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

A085 Operation mode

selection

Two options:
00 Normal operation
01 Energy-saver operation

✘ ✘

00

00

00

>A085 RUN

MODE NOR

A086 Energy saving mode

tuning

Range is 0.0 to 100 sec.

✔ ✔ 50.0 50.0 50.0

sec.

>A086 RUN

ECO 0050.0s