Hitachi L300P User Manual

Page 172

Advertising
background image

Using Intelligent Output Terminals

Oper

ations

a

nd Moni

tor

ing

4–42

The alarm output terminals operate as shown below (left) by default. The contact logic can be
inverted as shown (below right) by using the parameter setting C036. The relay contacts
normally open (N.O.) and normally closed (N.O.) convention uses “normal” to mean the
inverter has power and is in Run or Stop Mode. The relay contacts switch to the opposite
position when it is in Trip Mode or when input power is OFF.

N.C. contacts (after initialization)

N.O. contact (inverted by C036 setting)

During normal running

When an alarm occurs or

power is turned OFF

During normal running or

power is turned OFF

When an alarm occurs

AL1

AL0 AL2

AL1

AL0 AL2

AL1

AL0 AL2

AL1

AL0 AL2

Contact

Power

Run

State

AL0-

AL1

AL0-

AL2

N.C.

(after

initialize,

C036=01)

ON

Normal

Closed

Open

ON

Trip

Open

Closed

OFF

Open

Closed

Contact

Power

Run

State

AL0-

AL1

AL0-

AL2

N.O.

(set

C036=00)

ON

Normal

Open

Closed

ON

Trip

Closed

Open

OFF

Open

Closed

Advertising