ing

4–33

The figure below shows the operation during an overload restriction event. The overload
restriction level is set by B022 and B025. The overload restriction constant is the time to decel-
erate to 0Hz from maximum frequency. When this function operates, the acceleration time will
be longer than the normal acceleration time.

NOTE: The Overload Advance Notice function for intelligent outputs is related to Overload
Restriction operation, discussed in

“Overload Advance Notice Signal” on page 4–39

.

Valid for inputs:

C001, C002, C003, C004,
C005

Required
settings:

B021, B022, B023 (Mode 1),
B024, B025, B026 (Mode 2)

Notes:
If the overload restriction constant (B023 or

B026) is set too short, an over-voltage trip
during deceleration will occur due to regener-
ative energy from the motor.

When an overload restriction occurs during

acceleration, the motor will take longer to
reach the target frequency, or may not reach
it. The inverter will make the following
adjustments:
a) Increase the acceleration time
b) Raise torque boost
c) Raise overload restriction level

Opt.

Code

Symbol

Function Name

Input

State

Description

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

OLR

Example (requires input configuration—
see page

3–43

):

Overload

restriction level

Maximum

frequency

Output

frequency

Target frequency

Deceleration rate at overload restriction

Deceleration rate

at overload restriction

A004

F001

B022 / B025

B023 / B026

B022 / B025

t