NOTE: An inverter powered by a portable or emergency diesel power generator may result in a
distorted power waveform, overheating the generator. In general, the generator capacity should
be at least five times that of the inverter (kVA).

CAUTION: Be sure that the input voltage matches the inverter specifications:
• Three phase 200 to 240V 50/60Hz
• Three phase 380 to 480V 50/60Hz

CAUTION: Be sure not to power a three-phase-only inverter with single phase power. Other-
wise, there is the possibility of damage to the inverter and the danger of fire.

CAUTION: Be sure not to connect an AC power supply to the output terminals. Otherwise,
there is the possibility of damage to the inverter and the danger of injury and/or fire.

CAUTION: Remarks for using ground fault interrupter breakers in the main power supply:
Adjustable frequency inverters with CE-filters (RFI-filter) and shielded (screened) motor
cables have a higher leakage current toward Earth GND. Especially at the moment of switching
ON this can cause an inadvertent trip of ground fault interrupter breakers. Because of the recti-
fier on the input side of the inverter there is the possibility to stall the switch-off function
through small amounts of DC current. Please observe the following:
•

Use only short time-invariant and pulse current-sensitive ground fault interrupter
breakers with higher trigger current.

•

Other components should be secured with separate ground fault interrupter breakers.

•

Ground fault interrupter breakers in the power input wiring of an inverter are not an

absolute protection against electric shock.

CAUTION: Be sure to install a fuse in each phase of the main power supply to the inverter.
Otherwise, there is the danger of fire.

CAUTION: For motor leads, ground fault interrupter breakers and electromagnetic contac-
tors, be sure to size these components properly (each must have the capacity for rated current
and voltage). Otherwise, there is the danger of fire.

Power Output

R

S

T

T1

T2

T3

U

V

W

L1

L3

NOTE:

L1, L2, L3:

Three-phase 200 to 240V 50/60 Hz
Three-phase 380 to 480V 50/60 Hz

L2

Power Input