“A” Group: Standard Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–24

NOTE: For A095 and A096 (and for 2nd motor settings), if you set a very rapid Acc1 or Dec1
time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or Dec2 before
reaching the target frequency. In that case, the inverter decreases the rate of Acc1 or Dec1 in
order to achieve the second ramp to the target frequency.

A096 Dec1 to Dec2 frequency

transition point

Output frequency at which
Decel1 switches to Decel2,
range is 0.00 to 400.0 Hz

✘ ✘

0.0

0.0

0.0

Hz

>A096 DECEL

CHFr 0000.00Hz

A296 Dec1 to Dec2 frequency

transition point, 2nd
motor

Output frequency at which
Decel1 switches to Decel2,
range is 0.00 to 400.0 Hz
(2nd motor)

✘ ✘

0.0

0.0

0.0

Hz

>A296 2DECEL

CHFr 0000.00Hz

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)