“F” Group: Main Profile Parameters

Configur

ing Dr

iv

e

P

a

ra

meters

3–8

“F” Group: Main Profile Parameters

The basic frequency (speed) profile is
defined by parameters contained in the
“F” Group as shown to the right. The
output frequency is set in Hz, but accel-
eration and deceleration are specified
seconds (the time to ramp from zero to
maximum frequency, or from maximum
frequency to zero). The motor direction
parameter determines whether the
keypad Run key produces a FW or RV
command. This parameter does not
affect the [FW] terminal or [RV] intelligent terminal function, which you configure separately.

Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the main
profile. Accel and decel values for an alternative profile are specified by using parameters Ax92
through Ax93. The motor direction selection (F004) determines the direction of rotation as
commanded only from the keypad. This setting applies to either motor profile (1st or 2nd) in
use at a particular time.

Output
frequency

F001

F002

F003

t

“F” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

F001

Output frequency
setting

Standard default target
frequency that determines
constant motor speed
Range is 0 to 360 Hz

✔ ✔ 0.00 0.00 0.00

Hz

>F001 SET-Freq.

TM 0000.00Hz

2FS 0000.00Hz

3FS 0000.00Hz

TM 0000.00Hz

JG 0000.00Hz

1S 0000.00Hz

15S 0000.00Hz

OP1 0000.00Hz

OP2 0000.00Hz

RS485 0000.00Hz

F002

Acceleration (1) time
setting

Standard default accelera-
tion
Range is 0.01 to 3600 sec.

✔ ✔ 30.0 60.0 30.0

sec.

>F002 ACCEL

TIME1 0030.00s

F202

Acceleration (1) time
setting, 2nd motor

Standard default accelera-
tion, 2nd motor
Range is 0.01 to 3600 sec.

✔ ✔ 30.0 60.0 30.0

sec.

>F202 2ACCEL

TIME1 0030.00s

F003

Deceleration (1) time
setting

Standard default decelera-
tion
Range is 0.01 to 3600 sec.

✔ ✔ 30.0 60.0 30.0

sec.

>F003 DECEL

TIME1 0030.00s

F203

Deceleration (1) time
setting, 2nd motor

Standard default decelera-
tion, 2nd motor
Range is 0.01 to 3600 sec.

✔ ✔ 30.0 60.0 30.0

sec.

>F203 2DECEL

TIME1 0030.00s

F004

Keypad Run key routing Two options; select codes:

00 Forward
01 Reverse

✘ ✘

00

00

00

>F004 DIG-RUN

SELECT FW