PID ON/OFF
and PID Clear

The PID loop function is useful for controlling motor speed to achieve constant flow, pressure,
temperature, etc. in many process applications. The PID Disable function temporarily suspends
PID loop execution via an intelligent input terminal. It overrides the parameter A071 (PID
Enable) to stop PID execution and return to normal motor frequency output characteristics. the
use of PID Disable on an intelligent input terminal is optional. Of course, any use of the PID
loop control requires setting PID Enable function A071=01.

The PID Clear function forces the PID loop integrator sum = 0. So, when you turn ON an intel-
ligent input configured as [PIDC], the integrator sum is reset to zero. This is useful when
switching from manual control to PID loop control and the motor is stopped.

CAUTION: Be careful not to turn PID Clear ON and reset the integrator sum when the inverter
is in Run Mode (output to motor is ON). Otherwise, this could cause the motor to decelerate
rapidly, resulting in a trip.

Opt.

Code

Symbol

Function Name

Input

State

Description

23

PID

PID Disable

ON

Disables PID loop execution

OFF

Allows PID loop execution if A71=01

24

PIDC

PID Clear

ON

Force the value of the integrator to zero

OFF

No change to PID loop execution

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

A071

Notes:
The use of [PID] and [PIDC] terminals are

optional. Use A071=01 if you want PID loop
control enabled all the time.

Do not enable/disable PID control while the

motor is running (inverter is in Run Mode).

Do not turn ON the [PIDC] input while the

motor is running (inverter is in Run Mode).

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

PID

PIDC

Example (requires input configuration—
see page

3–43

):