Overload restriction – Hitachi L300P User Manual

Page 162

Advertising
background image

Using Intelligent Input Terminals

Oper

ations

a

nd Moni

tor

ing

4–32

Overload
Restriction

The inverter constantly monitors the motor current during acceleration, deceleration, and
constant speed. If the inverter reaches the overload restriction level, it adjusts the output
frequency automatically to limit the amount of overload. This function prevents an over-current
trip by inertia during rapid acceleration or large changes in load at constant speed. It also
attempts to prevent an over-voltage trip on deceleration due to regeneration. It accomplishes
this by temporarily suspending deceleration and/or increasing the frequency in order to dissi-
pate regenerative energy. Once the DC bus voltage falls sufficiently, deceleration will resume.

OLR Parameter Selection – Two sets of overload restriction parameter settings and values are
available as outlined in the table below. Use the B021—B026 group of settings to configure the
two set of parameters as needed. By assigning the Overload Restriction function [OLR] to an
intelligent terminal, you can select the set of restriction parameters that is in effect.

.

Function

Function Code

Data or Range

Description

Set 1

Set 2

Overload Restriction
Operation Mode

B021

B024

00

Disable

01

Enabled during accel
and constant speed

02

Enabled during constant
speed

03

Enabled during accel,
constant speed, and
decel

Overload Restriction
Setting

B022

B025

Rated current * 0.5
to rated current * 2

Current value at which
the restriction begins

Deceleration Rate at
Overload Restriction

B023

B026

0.1 to 30 seconds

Deceleration time when
overload restriction
operates

Opt.

Code

Symbol

Function Name

Input

State

Description

39

OLR

Overload Restric-
tion Selection

ON

Selects Overload Restriction Set 2,
B024, B025, B026 settings in effect

OFF

Selects Overload Restriction Set 1,
B021, B022, B023 settings in effect