Additional analog input settings – Hitachi L300P User Manual

Page 96

Advertising
background image

L300P Inverter

Configur

ing Dr

iv

e

P

a

ra

met

e

rs

3–27

Additional
Analog Input
Settings

The parameters in the following table adjust the input characteristics of the analog inputs.
When using the inputs to command the inverter output frequency, these parameters adjust the
starting and ending ranges for the voltage or current, as well as the output frequency range.
Related characteristic diagrams are located in

“Analog Input Settings” on page 3–11

.

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

A101 [OI]–[L] input active

range start frequency

The output frequency corre-
sponding to the current input
range starting point.
Range is 0.00 to 400.0 Hz

✘ ✔ 00.0 00.0 00.0

Hz

>A101 INPUT-OI

EXS 0000.00Hz

A102 [OI]–[L] input active

range end frequency

The output frequency corre-
sponding to the current input
range ending point.
Range is 0.00 to 400.0 Hz

✘ ✔ 00.0 60.0 00.0

Hz

>A102 INPUT-OI

EXE 0000.00Hz

A103 [OI]–[L] input active

range start current

The starting point for the
current input range.
Range is 0 to 100%

✘ ✔

20.

20.

20.

%

>A103 INPUT-OI

EX%S 020%

A104 [OI]–[L] input active

range end current

The ending point for the
current input range.
Range is 0 to 100%

✘ ✔ 100. 100. 100.

%

>A104 INPUT-OI

EX%E 100%

A105 [OI]–[L] input start

frequency enable

Two options:
00 Use A101 start value
01 Use 0Hz

✘ ✔

01

01

01

Hz

>A105 INPUT-OI

LEVEL 0Hz

A111 [O2]–[L] input active

range start frequency

The output frequency corre-
sponding to the bipolar
voltage input range starting
point.
Range is –400. to 400. Hz

✘ ✔ 0.00 0.00 0.00

Hz

>A111 INPUT-O2

EXS +000.00Hz

A112 [O2]–[L] input active

range end frequency

The output frequency corre-
sponding to the bipolar
voltage input range ending
point.
Range is –400. to 400. Hz

✘ ✔ 0.00 0.00 0.00

Hz

>A112 INPUT-O2

EXE +000.00Hz

A113 [O2]–[L] input active

range start voltage

The starting point for the
bipolar voltage input range.
Range is –100 to 100%

✘ ✔ -100. -100. -100.

%

>A113 INPUT-O2

EX%S -100%

A114 [O2]–[L] input active

range end voltage

The ending point for the
bipolar voltage input range.
Range is –100 to 100%

✘ ✔ 100. 100. 100.

%

>A114 INPUT-O2

EX%E +100%