Input wiring examples, Forward run/ stop and reverse run/stop commands – Hitachi L300P User Manual

Page 141

Advertising
background image

L300P Inverter

Oper

ati
ons

and Monitor

ing

4–11

Input Wiring
Examples

The input wiring diagrams in this chapter are examples only. Default and non-default input
terminal assignments are noted throughout; your particular assignments may be different. The
wiring diagrams show the –xFU2/–FR model default [P24]–[PLC] jumper position (U.S./Jpn
versions), as shown below on the left. The common (return) for inputs is [CM1] in this case.
The diagram on the right shows the default jumper position and example input wiring for
–xFE2 models (Europe version). For this case, the common (return) for inputs is [P24]. Be sure
the jumper position and return terminal used match your application wiring needs.

Forward Run/
Stop and Reverse
Run/Stop
Commands

When you input the Run command via the dedicated terminal [FW], the inverter executes the
Forward Run command (high) or Stop command (low). When you input the Run command via
the programmable terminal [RV], the inverter executes the Reverse Run command (high) or
Stop command (low).

NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single Run
key issues a Run FWD command or Run REV command. However, it has no effect on the [FW]
and [RV] input terminal operation.

WARNING: If the power is turned ON and the Run command is already active, the motor
starts rotation and is dangerous! Before turning power ON, confirm that the external Run
command is not active.

5

3

1

4

2

FW

TH

PLC

P24

CM1

FW RV

5

3

1

4

2

FW

TH

PLC

P24

CM1

FW RV

Default jumper

position [P24]–[PLC]

and wiring example

(used throughout this

chapter)

–xFU2/–FR models (U.S./Jpn versions):

–xFE2 models (Europe version):

Default jumper

position [PLC]–[CM1]

and wiring example

return

return

Opt.

Code

Symbol

Function Name

State

Description

FW

Forward Run/Stop

ON

Inverter is in Run Mode, motor runs
forward

OFF

Inverter is in Stop Mode, motor stops

01

RV

Reverse Run/Stop

ON

Inverter is in Run Mode, motor runs
reverse

OFF

Inverter is in Stop Mode, motor stops

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

A002 = 01

Notes:
When the Forward Run and Reverse Run

commands are active at the same time, the
inverter enters the Stop Mode.

When a terminal associated with either [FW]

or [RV] function is configured for normally
closed
, the motor starts rotation when that
terminal is disconnected or otherwise has no
input voltage.

5

3

1

4

2

FW

TH

PLC

P24

CM1

FW RV

See I/O specs on page

4–8

.

Example: (default input configuration
shown—see page

3–43

):