Hitachi L300P User Manual

Page 81

Advertising
background image

“A” Group: Standard Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–12

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

A005 [AT] selection

Two options; select codes:
00 Select between [O] and

[OI] at [AT]

01 Select between [O] and

[O2] at [AT]

✘ ✘

00

00

00

>A005 AT

SELECT O/OI

A006 [O2] selection

Three options; select codes:
00 Independent
01 Only positive
02 Both positive and

negative

✘ ✘

00

00

00

>A006 O2

SELECT O2

A011 [O]–[L] input active

range start frequency

The output frequency corre-
sponding to the voltage input
range starting point
Range is 0.00 to 400.00 Hz

✘ ✔ 0.00 0.00 0.00

Hz

>A011 INPUT-O

EXS 0000.00Hz

A012 [O]–[L] input active

range end frequency

The output frequency corre-
sponding to the voltage input
range ending point
Range is 0.00 to 400.00 Hz

✘ ✔ 0.00 60.0 0.00

Hz

>A012 INPUT-O

EXE 0000.00Hz

A013 [O]–[L] input active

range start voltage

The starting point for the
voltage input range
Range is 0 to 100%

✘ ✔

0.

0.

0.

%

>A013 INPUT-O

EX%S 000%

A014 [O]–[L] input active

range end voltage

The ending point for the
voltage input range
Range is 0 to 100%

✘ ✔ 100. 100. 100.

%

>A014 INPUT-O

EX%E 100%

A015 [O]–[L] input start

frequency enable

Two options; select codes:
00 Use A011 start value
01 Use 0 Hz

✘ ✔

01

01

01

>A015 INPUT-O

LEVEL 0Hz

A016 External frequency filter

time constant

Range n = 1 to 30, where n =
number of samples for avg.

✘ ✔

8.

8.

8.

Sam-

ples

>A016 INPUT

F-SAMP 08