PID Loop Operation

Oper

ations

a

nd Moni

tor

ing

4–58

PID Loop Operation

In standard operation, the inverter uses a reference source selected by parameter A001 for the
output frequency, which may be a fixed value (F001), a variable set by the front panel potenti-
ometer, or value from an analog input (voltage or current). To enable PID operation, set A071 =
01. This causes the inverter to calculate the target frequency, or setpoint. An optional intelligent
input assignment (code 23), PID Disable, will temporarily disable PID operation when active.

A calculated target frequency can have a lot of advantages. It lets the inverter adjust the motor
speed to optimize some other process variable of interest, potentially saving energy as well.
Refer to the figure below. The motor acts upon the external process. To control that external
process, the inverter must monitor the process variable. This requires wiring a sensor to either
the analog input terminal [O] (voltage) or terminal [OI] (current).

When enabled, the PID loop calculates the ideal output frequency to minimize the loop error.
This means we no longer command the inverter to run at a particular frequency, but we specify
the ideal value for the process variable. That ideal value is called the setpoint, and is specified
in the units of the external process variable. For a pump application it may be gallons/minute,
or it could be air velocity or temperature for an HVAC unit. Parameter A075 is a scale factor
that relates the external process variable units to motor frequency. The figure below is a more
detailed diagram of the PID function.

PID

Calculation

Error

Setpoint

SP

PV

Freq.

Inverter

Output

Motor

External

Process

Sensor

Process Variable (PV)

Inverter

Analog input

Monitor

P gain

I gain

D gain

Analog input scaling

Voltage

O

OI

L

Current

A GND

PID V/I

input select

Process Variable

(Feedback)

Scale factor

Frequency

setting

Scale factor

Setpoint

(Target)

Scale factor

reciprocal

Multi-speed

settings

Standard

setting

Frequency

source select

Potentiometer

on keypad

Error

[AT]

V/I input

select

PV

SP

A001

A075

F001

F001

1/A075

A020 to A035

A072

A073

A075

D004

A074

A076

A011

A015

A012

A013 A014

A071

PID Enable

C023

PID Disable

optional

intelligent input

PID

Normal