Determining wire and fuse sizes – Hitachi L300P User Manual

Page 53

Advertising
background image

Step-by-Step Basic Installation

In

v

e

rt

er Moun

ting

and Install

a

tion

2–14

Determining Wire
and Fuse Sizes

This section includes tables for 200V class and 400V class inverters (on the next page). The
following notes will help you read the tables in this section:

• Locate the row corresponding to the motor size and particular inverter in your application.

The maximum motor current determines the recommended wire sizes.

• The length column specifies that some inverters can optionally use a smaller wire gauge if

the wires are shorter than 10m and the inverter is located in an enclosure.

• Power Lines columns include wires connecting to terminals [R, S, T, U, V, W, P, PD, and N].

Only power input and motor leads will be fused: [R, S, T, U, V, and W]. The breaker ratings
(GFI—ground fault interrupter) are slightly higher than fuse ratings to allow for nominal
surges without tripping.

• The chassis ground columns list the Hitachi-recommended AWG and the minimal AWG for

UL conformity.

• The optional external braking resistor wiring only applies to a few models that have a built-

in braking unit. The other models use an optional external braking unit.

• Parallel wires increase effective wire gauge, and are denoted by “||” in the tables.

• Signal Lines, not listed in these tables, connect to the removable logic connector. The recom-

mended wire gauge for all wiring to the logic connector is 28 AWG (0.75 mm

2

). Be sure to

use shielded wire for any analog signals.

Motor

Output

200V

Inverter

Models,

L300P

Wiring *1

Power Lines *3

Chassis Ground

Brake Res.

HP

kW

Length

*4

AWG

*3

mm

2

*3

Fuse
(UL-

rated,

class J,

600V)

Breaker

( GFI

type) *2

AWG,

rec.

AWG,

UL

mm

2

AWG

mm

2

2

1.5

–015LFU2

14

2

10A

15A

16

14

1.25

14

2

3

2.2

–022LFU2

14

2

15A

20A

16

14

1.25

14

2

5

3.7

–037LFU2

10

3.5

20A

30A

10

12

3.5

10

3.5

7.5

5.5

–055LFU2

8

5.5

30A

50A

8

10

5.5

8

5.5

10

7.5

–075LFU2

6

8

40A

60A

8

10

8

8

5.5

15

11

–110LFU2

4

14

60A

75A

4

10

14

8

5.5

20

15

–150LFU2

≥10m

2

22

70A

100A

3

8

22

8

5.5

< 10m

4

(110°C)

14

(110°C)

25

18.5

–185LFU2

4 || 4

14 || 2

90A

100A

3

8

22

30

22

–220LFU2

1/0

38

100A

150A

2

8

30

40

30

–300LFU2

≥10m

2 || 2

22 || 22

150A

200A

2

6

30

< 10m

2

(110°C)

30

(110°C)

50

37

–370LFU2

≥10m

1 || 1

30 || 30

175A

225A

1/0

6

50

<10m

1

(110°C)

38

(110°C)

60

45

–450LFU2

1 || 1

(75°C)

38 || 38

200A

225A

3/0

6

80

75

55

–550LFU2

≥10m

2/0 || 2/0

60 || 60

250A

350A

3/0

4

80

< 10m

3/0

(110°C)

80

(110°C)

Advertising