Troubleshooting

T

roub

leshooting

and Maintenance

6–4

The motor speed will not reach the

target frequency (desired speed).

If using the analog input, is there

current or voltage at [O] or [OI]?

Check the wiring.
Check the potentiometer or

signal generating device.

Is the load too heavy?

Reduce the load.
Heavy loads activate the

overload restriction feature
(reduces output as needed).

Is the inverter internally limiting the

output frequency?

Check max frequency setting

(A004)

Check frequency upper limit

setting (A061)

If using analog inputs, check

their settings (A101– A104) or
(A111–A114), or (A011–
A014)

The rotation is unstable.

Is the load fluctuation too great?

Is the supply voltage unstable?
Is the problem occurring at a particular

frequency?

Does the instability occur at various

frequencies?

Increase the motor capacity

(both inverter and motor).

Fix power supply problem.
Change the output frequency

slightly, or use the jump
frequency setting to skip the
problem frequency.

Try adjusting H006 up or

down.

See

“Adjusting Motor Stabil-

ity” on page 4–57

.

The RPM of the motor does not

match the inverter output

frequency setting.

Is the maximum frequency setting

A004 correct?

Does the monitor function D001

display the expected output frequency?

Verify the V/F settings match

motor specifications.

Make sure all scaling (such as

A011 to A014) is properly set.

A parameter

will not

change after

an edit

(reverts to old

setting).

True for certain
parameters

Is the inverter in Run Mode? Some

parameters cannot be edited during
Run Mode.

Put inverter in Stop Mode

(press the Stop/reset key). Then
edit the parameter.

True for all
parameters

If you’re using the [SFT] intelligent

input (software lock function)—is the
[SFT] input ON?

Change the state of the SFT

input, and check the B031
parameter (SFT mode).

Symptom/condition

Probable Cause

Solution