Setting motor constants, Introduction, Adjusting motor stability – Hitachi L300P User Manual

Page 187: Setting motor constants 4–57

Advertising
background image

L300P Inverter

Oper

ati
ons

and Monitor

ing

4–57

Setting Motor Constants

Introduction

The inverter has two separate motor constant sets named 1st, and 2nd. The 1st motor constant
set is the default, while the SET intelligent input selects the 2nd motor constant set. The follow-
ing table lists the V/f characteristic control methods:

The following table lists the parameters associated with motor constant settings. Set each
constant according the motor type in the application. When connecting more than one motor (in
parallel) to the inverter, set the constant values that are closest to the total capacity of the
combined motors.

Adjusting Motor
Stability

Observe the motor for instability, particularly when it is rotating at constant speed. A common
symptom of instability, sometimes called “hunting,” is marked by a “rattling” sound in the
motor. To correct the instability, you can adjust some of the parameters listed above.

• Check the motor capacity (H003 / H203), and ensure it matches the capacity of your motor.

• Check the motor poles setting (H004 / H204), and ensure it matches your motor.

• If you are using a stabilization constant (H006 / H206) that is lower than the default setting,

trying raising it gradually up to the default value.

• If the motor you are using is greater than the rated capacity of the inverter, lower the value of

H006 / H206.

• If instability persists after you have checked the items above, try the procedures in the table

below. As soon as adjusting a parameter seems to produce stability, don’t change the param-
eter further. If adjusting a parameter has no effect, restore it to its original (or default) value.

V/f Characteristic Control Method

1st motor

2nd motor

V/f constant torque

V/f variable torque

V/f free-setting curve

Func.

Name

Data

Notes

A044 /

A244

V/f characteristic curve selection,

1st / 2nd motors

00

V/f constant torque

01

V/f variable torque

02

V/f free-setting curve

H003

Motor capacity, 1st motor

0.2 – 75

Units: kW

H203

Motor capacity, 2nd motor

0.2 – 75

Units: kW

H004

Motor poles setting, 1st motor

2 / 4 / 6 / 8

Units: poles

H204

Motor poles setting, 2nd motor

2 / 4 / 6 / 8

Units: poles

H006

Motor stabilization constant, 1st
motor

100

H206

Motor stabilization constant, 2nd
motor

100

Func.

Name

Data Range

Procedure

A045

Output gain

20 – 100

Lower this value

B083

Carrier frequency

0.5 – 8.0

Lower this value

H006 / H206

Motor stabilization constant

0 – 255

Lower or raise this value