Analog input current/voltage select – Hitachi L300P User Manual

Page 155

Advertising
background image

L300P Inverter

Oper

ati
ons

and Monitor

ing

4–25

Analog Input
Current/Voltage
Select

The [AT] terminal operates in conjunction with parameter setting A005 to determine the analog
input terminals that are enabled for current or voltage input. Setting A006 determines whether
the signal will be bipolar, allowing for a reverse direction range. Note that current input signal
cannot be bipolar and cannot reverse direction (must use [FW] and [RV] command with current
input operation). The following table shows the basic operation of the [AT] intelligent input.
Please refer to

“Analog Input Operation” on page 4–51

for more information on bipolar input

configuration, and the operating characteristics of analog inputs.

Opt.

Code

Symbol

Function Name

Input

State

Description

16

AT

Analog Input
Voltage/current
Select

ON

With A005 = 00, [AT] will enable

terminals OI–L for current input,
4 to 20mA

With A005=01, [AT] will enable termi-

nals [O2]–[L] for voltage input

OFF

Terminals [O]–[L] are enabled for voltage
input (A005 may be equal to 00 or 01) in
this case

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

A001 = 01
A005 = 00 / 01
A006 = 00 / 01 / 02

Notes:
Be sure to set the frequency source setting

A001=01 to select the analog input terminals.