Using Intelligent Input Terminals

Oper

ations

a

nd Moni

tor

ing

4–18

Two-stage
Acceleration and
Deceleration

When terminal [2CH] is turned ON, the
inverter changes the rate of acceleration and
deceleration from the initial settings (F002
and F003) to use the second set of accelera-
tion/deceleration values. When the terminal
is turned OFF, the inverter is returned to the
original acceleration and deceleration time
(F002 acceleration time 1, and F003 decel-
eration time 1). Use A092 (acceleration
time 2) and A093 (deceleration time 2) to
set the second stage acceleration and decel-
eration times.

In the graph shown above, the [2CH] signal becomes active during acceleration. This causes the
inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).

Opt.

Code

Symbol

Function Name

Input

State

Description

09

2CH

Two-stage Accelera-
tion and Decelera-
tion

ON

Frequency output uses 2nd-stage accelera-
tion and deceleration values

OFF

Frequency output uses the initial accelera-
tion 1 and deceleration 1 values

Valid for inputs:

C001, C002, C003, C004,
C005

Required
settings:

A092, A093, A094=0

Notes:
Function A094 selects the method for second

stage acceleration. It must be set = 00 to
select the input terminal method in order for
the 2CH terminal assignment to operate.

[2CH]

Switches

Output

frequency

[FW, RV]

target frequency

second

initial

t

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

2CH

Example (requires input configuration—