Item

200V Class Specifications

L300P inverters, 200V models, UL ver.

015LFU2

022LFU2

037LFU2

055LFU2

075LFU2

Applicable motor size, 4-pole *2

HP

2

3

5

7.5

10

kW

1.5

2.2

3.7

5.5

7.5

Rated capacity (200/240V) kVA

2.5 / 3.1

3.6 / 4.3

5.7 / 6.8

8.3 / 9.9

11 / 13.3

Rated input voltage

3-phase: 200 to 240V ±10%, 50/60 Hz ±5%

Rated input current (A)

8.3

12

18

26

35

Rated output voltage *3

3-phase (3-wire) 200 to 240V (corresponding to input voltage)

Rated output current (A)

7.5

10.5

16.5

24

32

Efficiency at 100% rated output, %

92.3

93.2

94.0

94.4

94.6

Watt loss,
approximate (W)

at 70% output

102

127

179

242

312

at 100% output

125

160

235

325

425

Dynamic braking
approx. % torque,
short time stop *7

without ext. res.

50%

20%

with external res.

200%

160%

100%

80%

DC braking

Variable operating frequency, time, and braking force

Weight

kg / lb

3.5 / 7.7

3.5 / 7.7

3.5 / 7.7

3.5 / 7.7

5 / 11

Item

200V Class Specifications

L300P inverters, 200V models, UL ver.

110LFU2

150LFU2

185LFU2

220LFU2

300LFU2

Applicable motor size, 4-pole *2

HP

15

20

25

30

40

kW

11

15

18.5

22

30

Rated capacity (200/240V) kVA

15.2 / 18.2

20.0 / 24.1

25.2 / 30.3

29.4 / 35.3

39.1 / 46.9

Rated input voltage

3-phase: 200 to 240V ±10%, 50/60 Hz ±5%

Rated input current (A)

48

64

80

94

124

Rated output voltage *3

3-phase (3-wire) 200 to 240V (corresponding to input voltage)

Rated output current (A)

44

58

73

85

113

Efficiency at 100% rated output, %

94.8

94.9

95

95

95

Watt loss,
approximate (W)

at 70% output

435

575

698

820

1100

at 100% output

600

800

975

1150

1550

Dynamic braking
approx. % torque,
short time stop *7

without ext. res.

10%

10%

10%

10%

10%

with external res.

55%

50%

with external res.
and braking unit

25–170%

25–150%

55–110%

DC braking

Variable operating frequency, time, and braking force

Weight

kg / lb

5 / 11

5 / 11

12 / 26.4

12 / 26.4

12 / 26.4